Home  /  Insight  /  03

Insight 03

Energy — pool halls use more electricity per square metre than any other building

Conventional indoor pool halls are among the most energy-intensive building types we have. Norwegian research documents an average consumption of 3,000–4,000 kWh per square metre of water area per year — and with tightened air change requirements it will rise further.

What does it cost to heat the air?

The largest single item is usually air: cleaning, replacing and heating the large volumes needed to keep the indoor climate acceptable. On top of that comes heating the pool water itself, lighting and the operation of technical systems.

Average, statistics from facilities in operation3,000–4,000 kWh/m²/yr
Reference facility to Norwegian TEK10, calculated~2,800 kWh/m²/yr
With modern heat recovery1,600–1,825 kWh/m²/yr

For comparison, an average Norwegian detached house uses around 130–150 kWh per square metre of floor area per year. A conventional pool hall therefore uses twenty to thirty times more energy per square metre of water area.

An expensive precondition

The reason for the high air-related energy use is trichloramine and other volatile disinfection by-products formed when chlorine reacts with organic material from bathers. These compounds are harmful and must be kept down.

The decisive point is that trichloramine cannot be filtered out. Activated carbon and other filters rapidly lose effectiveness in the warm, humid environment of a pool hall. The only effective measure is dilution: the air must be replaced with fresh outdoor air. Ventilation in pool halls is therefore not about filtering, but about continuously replacing large volumes.

Revised recommendations in Byggforskserien 552.315 tighten the requirements for air volumes and fresh-air proportion further, with increased supply directly over the water surface. The consequence is unambiguous: more fresh air in means more cold outdoor air to heat. For facilities already using 3,000–4,000 kWh/m² a year, new ventilation requirements mean a further rise in the electricity bill, with no energy-efficient shortcuts.

Heat loss that goes unused

Another familiar problem is heat loss from the pool into basements and plant rooms. The heat that leaks out is not necessarily put to use, and in practice ends up as wasted energy. Paradoxically, the same heat loss often raises the temperature in plant rooms so far that cooling units have to be installed as well. The result is a facility that heats and cools at the same time.

We heat only what needs heating

Our pools are built on a different principle. Here only the pool water is heated — not a large volume of air, not a hall, not the surrounding rooms. Walls and floor have an integrated foam core in the sandwich construction, which insulates and keeps the heat in the water.

At closing time a robust insulating cover is rolled across the surface. That removes most of the heat loss to air, which is otherwise the dominant loss for an outdoor pool. The combination of well-insulated surfaces and an effective surface cover means the heat supplied stays in the system for a long time.

Because the facilities stand outdoors, the same requirements for ventilation and air change do not apply. There is no hall air to keep below limit values, no large building envelope to heat or cool, and no plant rooms collecting heat loss.

Liquid to liquid gives a high coefficient

Heating uses liquid-to-liquid heat exchange. That gives a substantially higher coefficient of performance than solutions that must exchange between air and liquid, because liquid is a far more effective medium for transferring heat. Every kilowatt-hour of electricity therefore yields more heat in the pool water.

With seawater or ground source as the heat source, heating costs can be kept very low, including for a facility open through the winter. The combination of low energy demand, effective heat exchange and a renewable source gives an energy profile far below what a conventional pool hall can achieve — while the pool is available all year.

SourcesNTNU Open — Swimming pools and energy efficiency requirements · Gode idrettsanlegg — Energy use in Norwegian pool halls, Wolfgang Kampel (2015) · Byggforskserien 552.315 (SINTEF) · WHO air quality limit for NCl₃.

Each of the four articles takes on a different side of the same calculation.

See all the articles